求翻译:The actual problem for SSL is that when ever the frequency is falling below 47 Hz, the DCS power supply is swicthing off. Hence they are not able to get data from DCS for review and analyse the reason of trips. The DCS supply is coming from UPS. Normally UPS shall supply power by converting incoming AC to DC then DC t是什么意思?

待解决 悬赏分:1 - 离问题结束还有
The actual problem for SSL is that when ever the frequency is falling below 47 Hz, the DCS power supply is swicthing off. Hence they are not able to get data from DCS for review and analyse the reason of trips. The DCS supply is coming from UPS. Normally UPS shall supply power by converting incoming AC to DC then DC t