求翻译:The stator ground protection faults occurred twice in a 600MW generator. After extraction of rotor, it was found that the connection part of the stator bar with lead wire had been blown, and two fixed bolts fitting the lead wire have completely loosened. For analysis of ground-fault reasons, the generator stator end vi是什么意思?![]() ![]() The stator ground protection faults occurred twice in a 600MW generator. After extraction of rotor, it was found that the connection part of the stator bar with lead wire had been blown, and two fixed bolts fitting the lead wire have completely loosened. For analysis of ground-fault reasons, the generator stator end vi