求翻译:5.3.3 Unless the actual impedance of a transformer is known from transformer tests, 7.5% transformer impedance tolerance shall be used so that the specified design impedance is increased by 7.5% for load flow and motor starting calculations and decreased by 7.5% for short-circuit calculations.是什么意思?

待解决 悬赏分:1 - 离问题结束还有
5.3.3 Unless the actual impedance of a transformer is known from transformer tests, 7.5% transformer impedance tolerance shall be used so that the specified design impedance is increased by 7.5% for load flow and motor starting calculations and decreased by 7.5% for short-circuit calculations.